CE marking of transformers: which directives apply and what the declaration must contain
A distribution transformer is CE-marked under the Low Voltage, EMC, RoHS and Ecodesign rules. What each one requires, what a valid EU declaration of conformity looks like and the red flags to watch for on imported units.
The CE mark on a transformer nameplate is the manufacturer's statement that the product meets every applicable EU rule. For a distribution transformer that is a specific and short list – and each item is verifiable. Here is what should be behind the mark.
The applicable EU acts
| Act | What it requires for a transformer | Harmonised standard |
|---|---|---|
| Low Voltage Directive 2014/35/EU | Safety of the LV side (up to 1 000 V AC): insulation, clearances, terminals, earthing | EN IEC 60076 series, EN 50588-1 |
| EMC Directive 2014/30/EU | Transformers are passive; a statement of inherently benign EMC behaviour is normally sufficient | — |
| RoHS Directive 2011/65/EU | No restricted substances (lead, cadmium, mercury, hexavalent chromium…) above thresholds | EN IEC 63000 |
| Ecodesign Regulation (EU) 2019/1783 | Maximum no-load and load losses (Tier 2 since 1 July 2021); required information on nameplate and documentation | EN 50708 series |
The Machinery Regulation, the Pressure Equipment Directive and the ATEX Directive do not apply to standard distribution transformers.
What the EU declaration of conformity must contain
- Product identification: type, serial number, rated power and voltages.
- Name and address of the manufacturer (and of the importer, if the manufacturer is outside the EU).
- The statement that the declaration is issued under the sole responsibility of the manufacturer.
- The list of EU acts – as above – and the harmonised standards applied, with their dates.
- For Ecodesign: the reference to Regulation (EU) 2019/1783 and the declared P0 and Pk.
- Place, date, name and signature of the authorised person.
The declaration must be in a language accepted by the country of installation; English is accepted in most EU states, but Poland, Germany, France and Italy may require a translation for public tenders.
Red flags
- A "CE certificate" issued by a test laboratory. There is no such thing – CE is a self-declaration; laboratories issue test reports, not CE certificates.
- A declaration without serial numbers or with a generic product description.
- Losses on the nameplate that exceed the Tier 2 table – the transformer cannot legally be placed on the EU market.
- No Ecodesign reference at all on a unit delivered after July 2021.
- A manufacturer address outside the EU and no named EU importer.
Ecodesign also requires specific information on the nameplate and in the documentation: rated power, P0, Pk, the applicable tier, and – for units above 3 150 kVA – the peak efficiency index. Check the nameplate photo before you accept a delivery.
How Keynetgrid documents conformity
Every PNACHO transformer is delivered with an EU declaration of conformity covering the LVD, EMC, RoHS and Ecodesign requirements, referencing EN IEC 60076, EN 50588-1 and EN 50708, together with the routine test report that proves the declared losses for that serial number. The documents are in English; Polish and German versions are available on request. Details are in the "Documents" section of every product page in the oil-immersed and cast-resin ranges.
Further reading: Transformer documentation: FATs, EU Declaration, manual and responsibility (energeks.com, EN) · Dokumentacja tranformatora - certyfikaty, deklaracje CE, DTR i odpowiedzialność (energeks.pl, PL)
Request a quote for your PNACHO transformer
Send us rated power, voltages and the site of installation – our engineers will select the right configuration and send a quote within 24 hours.