Ecodesign Tier 2 explained: the loss limits every EU transformer must meet

Regulation (EU) 2019/1783 sets maximum no-load and load losses for transformers sold in the EU since July 2021. Here are the Tier 2 tables for oil-immersed and cast-resin units and what they mean for your bill.

September 11, 2026
Ecodesign Tier 2 loss limits – Keynetgrid blog

"Tier 2" appears on every PNACHO data sheet. It is not a marketing badge – it is the second, stricter stage of the EU Ecodesign regulation for power transformers, mandatory for every unit placed on the EU market since 1 July 2021. This article explains what the regulation requires and how to read the numbers.

What the regulation covers

Commission Regulation (EU) 2019/1783 (which replaced 548/2014) applies to power transformers with a minimum rating of 1 kVA used in 50 Hz transmission and distribution networks. For distribution transformers up to 3 150 kVA it sets maximum no-load losses (P0) and maximum load losses (Pk). Tier 1 applied from 2015; Tier 2 tightened the limits from July 2021. A transformer that exceeds either limit cannot be CE-marked and cannot legally be installed in the EU.

Tier 2 limits – oil-immersed, Um ≤ 24 kV

Rated powerMax. load losses PkMax. no-load losses P0
25 kVA600 W63 W
50 kVA750 W81 W
100 kVA1 250 W130 W
160 kVA1 750 W189 W
250 kVA2 350 W270 W
400 kVA3 250 W387 W
630 kVA4 600 W540 W
800 kVA6 000 W585 W
1 000 kVA7 600 W693 W
1 250 kVA9 500 W855 W
1 600 kVA12 000 W1 080 W
2 000 kVA15 000 W1 305 W
2 500 kVA18 500 W1 575 W

Ratings between the table values (for example 40 or 63 kVA) are interpolated linearly, as the regulation allows.

Tier 2 limits – dry-type (cast resin), Um ≤ 24 kV

Rated powerMax. load losses PkMax. no-load losses P0
100 kVA1 800 W252 W
160 kVA2 600 W360 W
250 kVA3 400 W468 W
400 kVA4 500 W675 W
630 kVA7 100 W990 W
800 kVA8 000 W1 170 W
1 000 kVA9 000 W1 395 W
1 250 kVA11 000 W1 620 W
1 600 kVA13 000 W1 980 W
2 000 kVA16 000 W2 340 W
2 500 kVA19 000 W2 790 W

Why no-load losses matter more than they look

Load losses scale with the square of the load; no-load losses are constant from the moment the transformer is energised. A 630 kVA oil unit at the Tier 2 limit burns 540 W × 8 760 h = 4 730 kWh a year even if nothing is connected. At 0.15 €/kWh that is about 700 € per year, 21 000 € over 30 years – more than the purchase price. This is why the regulation cut no-load limits by 10 % between Tier 1 and Tier 2 and why the value is printed on every PNACHO product page.

Tier 2 values are maximum values. A manufacturer may guarantee lower losses; a routine test on every unit confirms the actual figures, and the test report is part of the delivery.

What to ask for in a tender

  • Guaranteed P0 and Pk at rated voltage and 75 °C, with tolerances per IEC 60076-1.
  • The EU declaration of conformity referencing Regulation (EU) 2019/1783.
  • The routine test report of the delivered unit, not a type-test report of a "similar" unit.

Every PNACHO-O and PNACHO-D transformer is specified to these limits and ships with all three documents.

EcodesignTier 2EU 2019/1783lossesefficiency