Ecodesign Tier 2 explained: the loss limits every EU transformer must meet
Regulation (EU) 2019/1783 sets maximum no-load and load losses for transformers sold in the EU since July 2021. Here are the Tier 2 tables for oil-immersed and cast-resin units and what they mean for your bill.
"Tier 2" appears on every PNACHO data sheet. It is not a marketing badge – it is the second, stricter stage of the EU Ecodesign regulation for power transformers, mandatory for every unit placed on the EU market since 1 July 2021. This article explains what the regulation requires and how to read the numbers.
What the regulation covers
Commission Regulation (EU) 2019/1783 (which replaced 548/2014) applies to power transformers with a minimum rating of 1 kVA used in 50 Hz transmission and distribution networks. For distribution transformers up to 3 150 kVA it sets maximum no-load losses (P0) and maximum load losses (Pk). Tier 1 applied from 2015; Tier 2 tightened the limits from July 2021. A transformer that exceeds either limit cannot be CE-marked and cannot legally be installed in the EU.
Tier 2 limits – oil-immersed, Um ≤ 24 kV
| Rated power | Max. load losses Pk | Max. no-load losses P0 |
|---|---|---|
| 25 kVA | 600 W | 63 W |
| 50 kVA | 750 W | 81 W |
| 100 kVA | 1 250 W | 130 W |
| 160 kVA | 1 750 W | 189 W |
| 250 kVA | 2 350 W | 270 W |
| 400 kVA | 3 250 W | 387 W |
| 630 kVA | 4 600 W | 540 W |
| 800 kVA | 6 000 W | 585 W |
| 1 000 kVA | 7 600 W | 693 W |
| 1 250 kVA | 9 500 W | 855 W |
| 1 600 kVA | 12 000 W | 1 080 W |
| 2 000 kVA | 15 000 W | 1 305 W |
| 2 500 kVA | 18 500 W | 1 575 W |
Ratings between the table values (for example 40 or 63 kVA) are interpolated linearly, as the regulation allows.
Tier 2 limits – dry-type (cast resin), Um ≤ 24 kV
| Rated power | Max. load losses Pk | Max. no-load losses P0 |
|---|---|---|
| 100 kVA | 1 800 W | 252 W |
| 160 kVA | 2 600 W | 360 W |
| 250 kVA | 3 400 W | 468 W |
| 400 kVA | 4 500 W | 675 W |
| 630 kVA | 7 100 W | 990 W |
| 800 kVA | 8 000 W | 1 170 W |
| 1 000 kVA | 9 000 W | 1 395 W |
| 1 250 kVA | 11 000 W | 1 620 W |
| 1 600 kVA | 13 000 W | 1 980 W |
| 2 000 kVA | 16 000 W | 2 340 W |
| 2 500 kVA | 19 000 W | 2 790 W |
Why no-load losses matter more than they look
Load losses scale with the square of the load; no-load losses are constant from the moment the transformer is energised. A 630 kVA oil unit at the Tier 2 limit burns 540 W × 8 760 h = 4 730 kWh a year even if nothing is connected. At 0.15 €/kWh that is about 700 € per year, 21 000 € over 30 years – more than the purchase price. This is why the regulation cut no-load limits by 10 % between Tier 1 and Tier 2 and why the value is printed on every PNACHO product page.
Tier 2 values are maximum values. A manufacturer may guarantee lower losses; a routine test on every unit confirms the actual figures, and the test report is part of the delivery.
What to ask for in a tender
- Guaranteed P0 and Pk at rated voltage and 75 °C, with tolerances per IEC 60076-1.
- The EU declaration of conformity referencing Regulation (EU) 2019/1783.
- The routine test report of the delivered unit, not a type-test report of a "similar" unit.
Every PNACHO-O and PNACHO-D transformer is specified to these limits and ships with all three documents.
Further reading: What does Ecodesign Tier2 mean and how does it change the approach to no-load losses in transformers? (energeks.com, EN) · Co oznaza Ecodesign Tier2 i jak to zmienia w podejście do strat jałowych dla transformatorów? (energeks.pl, PL)