Parallel operation of transformers: the five conditions and what happens if you ignore them
Running two distribution transformers in parallel doubles capacity and adds redundancy – if ratio, vector group, impedance and tap positions match. The rules, the tolerances and the circulating current you get when they do not.
Two 1 000 kVA transformers in parallel are often a better solution than one 2 000 kVA unit: if one fails, half the plant keeps running; maintenance can be done without a full outage; and the second unit can be added later when the load grows. The price is a set of rules that must be respected.
The five conditions
| Condition | Requirement | Effect of a mismatch |
|---|---|---|
| Same voltage ratio | Identical HV and LV rated voltages, same tap position | Circulating current even at no load |
| Same vector group (clock number) | Both Dyn11 or both Dyn5 | Short circuit between the LV sides |
| Similar short-circuit impedance | uk within ±10 % of each other | Unequal load sharing; the low-uk unit overloads first |
| Power ratio | Not larger than 3 : 1 | Small unit reaches its limit while the large one is half loaded |
| Same phase sequence | L1-L2-L3 connected identically on both sides | Short circuit |
Load sharing in numbers
Transformers in parallel share the load in proportion to their rating and in inverse proportion to their impedance. Two 1 000 kVA units with uk 6 % and 5.4 % (a 10 % deviation) carry 47 % and 53 % of the total load: at 2 000 kVA total the second unit runs at 1 060 kVA – a 6 % overload. That is why IEC 60076 recommends the ±10 % tolerance and why the routine test report, which states the measured uk, is worth reading before paralleling.
Circulating current from a ratio mismatch
If the two units are on different taps – one at +2.5 %, the other at 0 % – the 2.5 % voltage difference drives a current through both LV windings even with no load connected. With uk = 6 % on both, the circulating current is 2.5 / (6 + 6) = 21 % of rated current. It adds vectorially to the load current, heats both transformers and is invisible to the load. Always set both tap changers to the same position and lock them.
A common field error: replacing one of two old Dyn5 units with a new Dyn11 unit "because that is the standard now". The two must never be paralleled. Order the replacement with the same vector group – for PNACHO transformers Dyn5 is available on request at no extra cost.
Switchgear and protection
- Each transformer needs its own LV circuit breaker; the bus coupler between the two sections allows single-unit operation.
- The LV fault current is the sum of both contributions – recalculate the switchgear rating (for two 1 000 kVA units at 6 %: about 46 kA).
- Reverse-power or directional protection prevents one transformer from back-feeding a fault in the other.
Specifying a parallel pair
Order both units at the same time and from the same series. Two PNACHO-O 1000 kVA 21/0.42 kV units, for example, are built to the same drawing and tested in the same way; their measured impedances differ by far less than the 10 % tolerance. If you are adding a unit to an existing installation, send us the nameplate photo of the old transformer – we check ratio, group and impedance before we quote.