Technology

Short-circuit impedance uk: what 4 % or 6 % means for your installation

The impedance voltage decides fault current, voltage drop and parallel operation. Why distribution transformers up to 630 kVA have uk = 4 %, larger units 6 %, and how to use the figure in switchgear design.

September 15, 2026
Short-circuit impedance uk – Keynetgrid blog

On a PNACHO data sheet you will find uk = 4 % for oil-immersed units up to 630 kVA and uk = 6 % above that and for all cast-resin units. Few parameters are as important for the design of the low-voltage switchgear – and few are as often ignored.

Definition

The short-circuit impedance (impedance voltage) is the primary voltage, expressed as a percentage of rated voltage, that drives rated current through the transformer when the secondary is short-circuited. It is measured in the routine test at 75 °C reference temperature. It combines the resistive part (load losses) and – mostly – the leakage reactance between the windings.

Consequence 1: fault current on the LV side

With an infinitely strong MV network, the maximum symmetrical short-circuit current at the LV terminals is simply

Ik = In / uk

Rating (0.42 kV)Rated LV current InukMax. LV fault current Ik
250 kVA344 A4 %8.6 kA
630 kVA866 A4 %21.7 kA
1 000 kVA1 375 A6 %22.9 kA
1 600 kVA2 199 A6 %36.7 kA
2 500 kVA3 437 A6 %57.3 kA

The LV switchboard, its busbars and the circuit breakers must be rated for this current (plus the contribution of motors). This is why the impedance rises to 6 % at larger ratings: at 4 % a 2 500 kVA transformer would deliver 86 kA – beyond most standard switchgear.

Consequence 2: voltage drop under load

The same impedance causes a voltage drop across the transformer when current flows. At full load with cos φ = 0.8 the drop is roughly 0.8 × ur + 0.6 × ux; for a 630 kVA unit with uk = 4 % (ur ≈ 0.7 %, ux ≈ 3.9 %) that is about 2.9 % – within the ±5 % most installations tolerate, but worth checking for long LV feeders and for PV plants, where the voltage rises under generation.

Consequence 3: parallel operation

Transformers in parallel share the load in inverse proportion to their impedance. IEC practice: uk of the units should not differ by more than 10 % of each other, and the power ratio should not exceed 3:1. A 630 kVA (4 %) and a 1 000 kVA (6 %) unit can be paralleled only if the 630 kVA is accepted to run overloaded first.

The tap changer changes the ratio, not the impedance. Two transformers on different tap positions in parallel produce a circulating current – set both to the same tap.

Can uk be changed?

Yes, within limits. A higher impedance (e.g. 6 % instead of 4 % on a 630 kVA) reduces the fault current and lets you reuse an existing switchboard; a lower impedance reduces voltage drop. Both are custom windings with a longer lead time. The standard values on the PNACHO-O and PNACHO-D product pages follow IEC 60076-5 and the usual grid-operator specifications, so they fit standard switchgear without recalculation.

short-circuit impedanceukfault currentvoltage dropswitchgear
Share this article

Request a quote for your PNACHO transformer

Send us rated power, voltages and the site of installation – our engineers will select the right configuration and send a quote within 24 hours.

See the range